1Model 231 Multi-Sense®Wet-to-Wet Pressure Transducer978-263-1400; 800-257-3872www.setra.com; [email protected]
10ABCDMS1 50 25 10 5MS2 100 50 20 10MS3 250 125 50 25A B C DRANGESZEROOUTPUTABCD4-20 0-5 0-10 1-5A B C DBARA.REVSLOWBI-DIRSWAPPSINOR
116.0 RETURNING PRODUCTS FOR REPAIRPlease contact a Setra application engineer (800-257-3872, 978-263-1400) beforereturning unit for repair to review
12159, Swanson Road, Boxborough, MA 01719978-263-1400; 800-257-3872/www.setra.com; [email protected] Rev B 05/31/07CECECECECERoHS
2
3Contents1.0 GENERAL INFORMATION... 42.0 MECHANICAL INSTALLATION ...
4Installation GuideMulti-Sense® Model 231 SeriesWet-to-Wet Differential Pressure Transducers1.0 GENERAL INFORMATIONEvery Model 231 has been calibrated
52.3 Pressure FittingsTypically standard pipe fittings and installation procedures should be used.The Model 231 has 1/8” −NPTF internal fittings. The
63-Valve Manifold DescriptionManifold Block BrassValves (3) V1 for connection to + portV2 for connection to - portV3 for equalizing pressureValve Type
71/2” Conduit OpeningModel 231 - Outline Drawingin.mmFront ViewBottom ViewSide ViewFigure 35.61416.01520.39R 0.121.2311.7421.0241.6405.21311/8” NPTF2.
84.0 ELECTRICAL INSTALLATIONTo access the electrical connections, turn the screws on the top of the casecounter clockwise until the hinged cover can b
94.2 Electrical TerminationWiring: 3-Wire, 0 to 5, 0 to 10, 1-5 VDC and Remote ZeroThe Model 231 when configured for voltage output is a 3-wire circu