Setra Systems Model 3100/3200
Pressure Transducer
1.0 GENERAL INFORMATION
Every Model 3100/3200 has been tested and calibrated before shipment.
Setra Systems 3100/3200 pressure transducers sense gauge pressure and con-
vert this pressure dierence to a proportional high level analog output. The
following standard output and excitation versions are oered:
EXCITATION OUTPUT
10 to 30 VDC 4 to 20 mA
5 VDC ±10% 0.5 to 4.5 Ratiometric
0 to 10 VDC
0.5 to 4.5 VDC
2V above Full Scale to 30 VDC max @ 4.5mA 0 to 5 VDC
1 to 6 VDC
1 to 5 VDC
2mV/V (nominal)
2.0 MECHANICAL INSTALLATION
2.1 Media Compatibility
Model 3100/3200 transducers are designed to be used with any gases or liquids
compatible with 17-4 PH Stainless Steel.
2.2 Environment
The operating temperature limits of the 3100/3200 are -40°F to +250°F
(-40°C to +125°C). The compensated temperature range is -40°F to +250°F
(-40°C to +125°C).
Ingress Protection: all transducers/transmitters have a minimum IP rating
of IP65 in accordance with BS EN 60529.
2.2 Electrical (See Diagram A, page 2 for electrical connections)
Cable Connectors: where client cable are used, the cable shield must be
terminated by the client. The shield should not be connected to the
transducer body.
Setra uses a 4-core color coded cable enclosed by a braided shield
terminated within the transducer housing. Conformance of requirement
with relation to the CE Mark, is only valid with Setras approved cable.
Frequency Response: <1ms for Conditioned Outputs.
Maximum Current Draw: 2-wire Transmitter = 20mA, Transducer in
voltage mode = 8mA, transducer in millivolt mode = 3.5mA
EMC Data: Meets the requirements of CE.
This product complies with EN61326-1 and EN61326-2-3 Electrical Equipment
for Measurement, Control and Laboratory use – EMC Requirements for Mini-
mum Requirements and Industrial Locations. Special caution should be taken to
meet Standard EN61000-4-5. Surge Immunity if any of the following conditions
apply to
Installation Guide