2.4 Installation of Pressure Fittings
Your transducer is designed for the most accurate operation when subjected
to pressures within the designated pressure range. Refer to page 4 for proof
pressure limits.
Standard sealants such as Teon pipe tape generally are satisfactory on NPT
threads. For the most sensitive pressure ranges, excessive high torquing of a
metal pressure tting may cause slight zero shift which may be trimmed out
using the zero adjustment. Use of a plastic tting often shows no noticeable
zero shift. The torquing eect does not appreciably aect linearity or sensitiv-
ity. The 3/4 in. wrench at (Hex) on the unit must be used when installing the
positive pressure tting.
3.0 ELECTRICAL INSTALLATION
3.1 Electrical Connections
ASM is available with a cable, or bayonet connector options having dierent
connector pin-outs shown in table below:
Code B3
(Standard)
Code B4
Option
Code B5
Option
Code B6
Option
Code B7
Option
Electrical Connection Wire
Color
Bayonet
Conn.
Pinout
Bayonet
Conn.
Pinout
Bayonet
Conn.
Pinout
Bayonet
Conn.
Pinout
Bayonet
Conn.
Pinout
Current Voltage
+EXC + EXC Red A A A C A
-EXC - EXC Black D B B D C
NA + Sig Out Green B C D A F
NA - Sig Out White C D C B E
Reserved for communication with SecureCal
TM
calibration module
SecureCal Blue E E E E B
SecureCal Brown F F F F D
Shield
Drain Wire
Ex-
posed
Case Case Case
CAUTION: Connecting -EXC to positive excitation and +Sig to negative excita-
tion at the same time may damage the unit.
3.2 Voltage Output Units
The Model ASM voltage units are a four-wire type circuit energized thru +EXC
and -EXC terminal with 0-5VDC or 0-10VDC analog output through the +SIG
Out and -SIG Out terminals.
3.3 Current Output Units
The Model ASM current units are a two-wire loop-powered 4 to 20mA current
output and deliver rated current into any external load of 0 to 800 ohms.