The current ows into the +EXC terminal and returns back to the power sup-
ply through the -EXC terminal (See Diagram 1). Note: The +SIG Out and -SIG
Out terminals are not used. The power supply must be a DC voltage source
with a voltage range between 9 and 30 VDC measured between the + and
- terminals. The unit is calibrated at the factory with a 24 VDC loop supply
voltage.
3.4 Cable for Bayonet Connectors
For good EMC performance, shielded cable shall be used and grounded to
earth ground. Cable shall only be used within a building and not be longer
than 30 m (100 ft.).
Diagram 1
Electrical Data
Signal Output Ranges 0-5 VDC, 0-10 VDC (4-wire); 4-20mA (2-Wire)
Nominal Excitation 24 VDC
Excitation Range 9-30 VDC (5 VDC & 4-20mA output)
15-30 VDC (10 VDC Output)
Current Consumption <23mA
Circuit Response Time <10ms (Voltage Version),
<80ms (4-20mA Version)
Warm-up, Environmental Within +/-0.02%FS after 15 min. Warm-up Time
Miswiring Reverse Excitation Protection
4.0. CALIBRATION
The ASM transducer is factory calibrated and should require no eld adjust-
ment if mounted in a vertical position. Whenever possible, any zero and/or
span osets should be corrected by software adjustment in the user’s control
system. However, ne zero and span adjustments can be made through use
of Secure-Cal
TM
accessory (purchased separately) for calibration access. The
Model ASM transducer zero oset is trimmed in the vertical position (pressure
port pointing downward) prior to shipping from factory.
4.1 Zero/Span Adjustments with Secure-Cal
TM
To make secure zero and span adjustments, attach SecureCal
TM
accessory to
ASM pressure transducer. (See Diagram 2).
+
_
9 to 30 VDC
ASM
Current
Monitoring
Device